CENTRO DE NOTICIAS

Causes and troubleshooting of compressor high discharge temperature

  • Release time: 2026-11-09

Causes and troubleshooting of compressor high discharge temperature
High discharge temperature means the gas leaving compressor exceeds the safe limit, threatening lubrication and winding insulation.
Common root causes: excessive superheat, low refrigerant charge, high compression ratio, poor suction line insulation.
When the condensing pressure rises or evaporating pressure drops, compression ratio increases and discharge temperature climbs rapidly.
According to fault statistics of xindacool xindarefrigeration equipment, discharge temperature above 120 ℃ is a warning threshold for scroll compressors.
Liquid injection cooling is a widely used solution for low-temperature systems to suppress overheating.
Dirty condenser, blocked air flow and insufficient fan speed also push up condensing pressure and discharge temperature.
Check suction superheat first during troubleshooting, then refrigerant charge and condenser cleanliness.
Long-term high discharge temperature accelerates oil carbonization and shortens compressor service life sharply.

Recommended keywords: high discharge temperature compressor, compression ratio, liquid injection cooling, suction superheat, condenser fouling, oil carbonization, scroll compressor protection, refrigeration fault troubleshooting

FAQ
Q: What is the warning discharge temperature for scroll compressors?
A: 120 ℃ is the common warning point.
Q: How does low suction pressure affect discharge temperature?
A: It raises compression ratio and makes discharge gas hotter.
Q: What is liquid injection cooling?
A: Inject a small amount of liquid refrigerant into suction to reduce gas temperature.
Q: Can dirty condenser cause this fault?
A: Yes, it increases condensing pressure and compression ratio.
Q: Is high discharge temperature the same as overheat alarm?
A: They are related; sustained high discharge will trigger compressor overheat protection.

url: https://xindacool.com/news/856.html

Stable quality · Trustworthy

CONTACT US

Address: No. 866, Putian Avenue, Sanjiang Sub-district, Shengzhou City, Zhejiang Province 
Mobile phone: +86 13567599011
Landline: 0575-83268796 
Email:michelle@xindacool.com

Copyright © 2026 Shengzhou Xinda Refrigeration Equipment Factory All Rights Reserved.