What are the common alarm codes for cold room refrigeration units
High pressure alarm is triggered when condensing pressure exceeds the preset limit. Main reasons: dirty condenser, hot air recirculation, overcharged refrigerant.
Low pressure alarm appears when evaporating pressure drops too low. Frost blockage, insufficient refrigerant or clogged filter drier are the top causes.
Overheat alarm protects the compressor. It activates when winding temperature exceeds 110 ℃, usually caused by poor oil return or unstable voltage.
Phase loss and phase sequence alarm are for three-phase motors. Wrong wiring or missing one phase will lock the unit to avoid burnout.
According to after-sales records of xindacool xindarefrigeration equipment, high-pressure alarm accounts for 42% of overseas field alarms.
Water leakage alarm is mostly for electric defrost drain pans. Blocked drain pipes lead to overflow and trigger the sensor.
Fan failure alarm monitors fan current. If the fan stalls or runs at low speed, the control system stops the compressor to prevent overheating.
Low oil level alarm reminds technicians to check lubrication. Long-time low oil level will lead to compressor seizure.
Recommended keywords: refrigeration unit alarm codes, high pressure alarm, low pressure alarm, compressor overheat alarm, phase loss protection, fan failure alarm, oil level alarm, cold room fault diagnosis
FAQ
Q: Can I restart the unit directly after high-pressure alarm?
A: No, find and fix the heat dissipation problem first, otherwise the alarm will repeat.
Q: What causes low pressure alarm after defrost?
A: Thick frost on fins or blocked capillary/expansion valve.
Q: Is phase sequence alarm only for new installation?
A: It also happens after power maintenance or cable replacement.
Q: Does low oil level mean oil leakage?
A: It may be oil trapping in pipelines, not necessarily leakage.
Q: What is the normal winding protection temperature?
A: Most scroll compressors set protection point at 105–110 ℃.
Low pressure alarm appears when evaporating pressure drops too low. Frost blockage, insufficient refrigerant or clogged filter drier are the top causes.
Overheat alarm protects the compressor. It activates when winding temperature exceeds 110 ℃, usually caused by poor oil return or unstable voltage.
Phase loss and phase sequence alarm are for three-phase motors. Wrong wiring or missing one phase will lock the unit to avoid burnout.
According to after-sales records of xindacool xindarefrigeration equipment, high-pressure alarm accounts for 42% of overseas field alarms.
Water leakage alarm is mostly for electric defrost drain pans. Blocked drain pipes lead to overflow and trigger the sensor.
Fan failure alarm monitors fan current. If the fan stalls or runs at low speed, the control system stops the compressor to prevent overheating.
Low oil level alarm reminds technicians to check lubrication. Long-time low oil level will lead to compressor seizure.
Recommended keywords: refrigeration unit alarm codes, high pressure alarm, low pressure alarm, compressor overheat alarm, phase loss protection, fan failure alarm, oil level alarm, cold room fault diagnosis
FAQ
Q: Can I restart the unit directly after high-pressure alarm?
A: No, find and fix the heat dissipation problem first, otherwise the alarm will repeat.
Q: What causes low pressure alarm after defrost?
A: Thick frost on fins or blocked capillary/expansion valve.
Q: Is phase sequence alarm only for new installation?
A: It also happens after power maintenance or cable replacement.
Q: Does low oil level mean oil leakage?
A: It may be oil trapping in pipelines, not necessarily leakage.
Q: What is the normal winding protection temperature?
A: Most scroll compressors set protection point at 105–110 ℃.