How to prevent oil migration in parallel compressor rack systems
Oil migration means lubricating oil flows from one compressor to another in parallel rack, leading to oil shortage.
Uneven suction gas velocity and different internal pressure of compressors are the main causes.
Oil equalizer pipe must be installed at the crankcase oil level position of all compressors.
According to commissioning specification of xindacool xindarefrigeration equipment, oil equalizer line should be same diameter as crankcase connection port.
Oil separator with oil return solenoid feeds oil back to the common crankcase circuit steadily.
Do not start compressors at different times randomly; the control program should manage startup sequence.
Obstructed oil equalizer pipe will break oil balance, some compressors run with too much oil and others lack oil.
Check oil sight glass of each compressor weekly during normal operation.
Recommended keywords: parallel rack oil migration, oil equalizer pipe, crankcase oil balance, refrigeration rack commissioning, oil return management, compressor oil sight glass, oil shortage protection, multi-compressor system
FAQ
Q: What is oil migration?
A: Oil transfers between compressors, causing uneven oil level.
Q: What component solves oil migration?
A: Oil equalizer pipe connected between crankcases.
Q: Does oil equalizer need insulation?
A: Usually no, keep it at the same temperature as crankcase.
Q: Can blockage of equalizer pipe cause compressor burnout?
A: Yes, some compressors will run without enough lubrication.
Q: Is oil separator enough without oil equalizer?
A: No, oil separator cannot replace crankcase oil equalizer.
Address: No. 866, Putian Avenue, Sanjiang Sub-district, Shengzhou City, Zhejiang Province
Mobile phone: +86 13567599011
Landline: 0575-83268796
Email:michelle@xindacool.com