CENTRO DE NOTICIAS

Function and maintenance of filter drier in refrigeration systems

  • Release time: 2026-11-09

Function and maintenance of filter drier in refrigeration systems
Filter drier is installed in liquid line to capture moisture, acid, solid particles and sludge inside the refrigeration circuit.
It protects the expansion valve capillary from ice blockage and prevents acid corrosion of compressor winding.
There are two common types: solid core filter drier and replaceable core filter drier.
According to xindacool xindarefrigeration equipment service standard, replaceable core type is preferred for large cold room units for easy maintenance.
After any pipeline opening, component replacement or refrigerant leakage repair, the filter drier must be renewed.
The indicator sight glass after drier shows moisture status. Green means dry; yellow indicates excessive moisture.
Overloaded filter drier will cause pressure drop in liquid line, insufficient refrigerant supply and poor cooling.
Do not reuse old filter cores. The molecular sieve will saturate and release absorbed water again.

Recommended keywords: filter drier refrigeration, liquid line filter drier, moisture indicator sight glass, molecular sieve core, acid capture, ice block prevention, replaceable filter drier, refrigerant circuit maintenance

FAQ
Q: When must the filter drier be replaced?
A: Every time the refrigeration loop is opened or after leakage repair.
Q: What does yellow indicator mean?
A: The system contains excessive moisture, need to change drier and re-vacuum.
Q: Can I clean and reuse filter drier?
A: No, molecular sieve cannot be regenerated on site.
Q: Where is the filter drier installed?
A: On the liquid pipe before the expansion valve.
Q: What happens if the drier is clogged?
A: Liquid supply reduces, cooling capacity drops and frost appears on the drier shell.

url: https://xindacool.com/news/868.html

Stable quality · Trustworthy

CONTACT US

Address: No. 866, Putian Avenue, Sanjiang Sub-district, Shengzhou City, Zhejiang Province 
Mobile phone: +86 13567599011
Landline: 0575-83268796 
Email:michelle@xindacool.com

Copyright © 2026 Shengzhou Xinda Refrigeration Equipment Factory All Rights Reserved.