How to prevent ice blockage in refrigeration pipelines
Ice blockage is caused by excessive moisture mixed in refrigerant. Water freezes at the expansion valve or capillary and blocks flow.
Moisture comes from incomplete vacuum pumping, leaking pipeline joints or wet refrigerant cylinder.
The filter drier is the core component to absorb water and acid. It must be replaced after system opening and maintenance.
According to after-sales cases of xindacool xindarefrigeration equipment, ice blockage mostly occurs within 1–3 months after new installation or repair.
If cooling works normally at first and then stops suddenly, and restarts after shutdown and warming up, it is typical ice blockage.
Do not add methanol to solve ice blockage for export food cold rooms. It contaminates oil and damages compressor.
Re-vacuum the whole system and install new filter drier with molecular sieve desiccant.
Keep refrigerant cylinders sealed and avoid storing them in humid outdoor environments.
Recommended keywords: ice blockage refrigeration system, moisture in refrigerant, filter drier replacement, molecular sieve desiccant, vacuum pumping moisture, methanol prohibition, capillary ice clog, expansion valve ice block
FAQ
Q: How to tell ice block from dirty block?
A: Ice block disappears after warming up; dirty block stays blocked permanently.
Q: Can methanol be used for emergency?
A: Not allowed for food cold rooms and export units, it damages compressor lubrication.
Q: How often replace filter drier?
A: Every time the pipeline is opened or refrigerant is drained.
Q: Where does moisture mainly enter?
A: Poor vacuum or leaking joints sucking humid air during negative pressure.
Q: Is ice block common in new systems?
A: Yes, if vacuum work is not strictly finished.