How to test refrigerant leakage for cold room systems
Soap bubble test is the basic on-site method. Apply soap water on joints, welds, valve ports and observe bubbles.
Electronic leak detector is more sensitive, suitable for detecting tiny leaks of R404A, R507A and R448A. It can find trace leakage that soap water misses.
Nitrogen pressure holding test is required before charging refrigerant. Keep pressure for 8 hours; pressure drop shall not exceed 0.02 MPa.
According to export inspection standards of xindacool xindarefrigeration equipment, all cold room units must pass nitrogen pressure test before shipment.
Leaks often occur at copper welds, flare nuts, valve stems and expansion valve sensing bulb pipelines.
If refrigerant leaks out, lubricating oil will escape together. Oil stains are intuitive clues for leak points.
Do not use oxygen for pressure test; only dry nitrogen is allowed to avoid explosion risk.
After repairing leakage, vacuum pumping is mandatory before recharging refrigerant, vacuum degree should reach below 500 microns.

Recommended keywords: refrigerant leak detection, soap bubble test, electronic leak detector, nitrogen pressure holding test, vacuum pumping standard, flare nut leakage, oil stain leak clue, cold room system inspection

FAQ
Q: How long is the nitrogen holding test time?
A: 8 hours as standard, some strict customers require 24 hours.
Q: Can I use compressed air for pressure test?
A: No, air contains moisture which will cause ice blockage in the expansion valve.
Q: Is oil stain always a leak point?
A: Yes, refrigerant dissolves compressor oil and oil seeps out together.
Q: What vacuum level is acceptable?
A: Below 500 microns before refrigerant charging.
Q: Which leak method works best for tiny leaks?
A: Electronic leak detector is more sensitive than soap water.

url: https://xindacool.com/news/874.html

Stable quality · Trustworthy

CONTACT US

Address: No. 866, Putian Avenue, Sanjiang Sub-district, Shengzhou City, Zhejiang Province 
Mobile phone: +86 13567599011
Landline: 0575-83268796 
Email:michelle@xindacool.com

Copyright © 2026 Shengzhou Xinda Refrigeration Equipment Factory All Rights Reserved.